Initialisation
Pre-Operational
Operational
Stopped
Einschalten
aus beliebigem
Zustand
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
After Power On and the initialization, the slaves are in the Pre-Operational state.
T
he transition (2) is automatic. The system bus master (frequency inverter or PLC/PC)
triggers the transition (3) to Operational state.
The transitions are controlled via NMT telegrams.
The identifier used for the NMT tele
g
rams is "0" and may only be used by the system
bus master for NMT telegrams. The telegram contains two data bytes.
Byte 0 Byte 1
CS (Command Specifier) Node-ID
Identifier = 0
With the statement of the node ID 0, the NMT command acts on the subscribe
r
selected via the node ID. If node ID = 0, all the subscribers are addressed. If Node-
ID = 0, all nodes are addressed.
Transition Command Command Specifier
(3) , (6) Start Remote Node 1
(4) , (7) Enter Pre-Operational 128
(5) , (8) Stop Remote Node 2
- Reset Node 129
- Reset Communication 130
Note: A frequency inverter defined as a system bus master only transmits the
command "Start Remote Node” with node ID = 0 (for all subscribers).
Transmission of the command is done after completion of the initialization
phase and the time delay
Boot-Up Delay 904 following it.