4.1.7 Error and warning behavior
The monitoring of the analog input signal necessary accordin
to the application is to
be configured via the parameter
Error/Warning behavior 563.
Operation mode Function
0 - Off The input signal is not monitored.
1 - Warning < 1 V / 2 mA
If the input signal is less than 1 V or 2 mA, there
is a warning message.
2 - Shutdown < 1 V / 2 mA
If the input signal is less than 1 V or 2 mA, there
is a warning message, the drive mechanism is
decelerated according to stopping behavior 1.
3 -
Fault switch-off
< 1 V / 2 mA
If the input signal is less than 1 V or 2 mA, there
is a warning and fault message and the drive
mechanism stops freely.
he monitorin
of the analo
input si
nal is active independent of the release of the
frequency inverter according to the operation mode selected.
In operation mode 2, the drive mechanism is decelerated independent of the stoppin
behavior set (Parameter Operation mode 630) accordin
to stoppin
behavior 1
(shutdown and switch-off). If the set holding time has expired, there is a fault mes-
sage. A repeat start of the drive mechanism is possible by switchin
the start si
nal on
and off if the fault has been cleared.
Operation mode 3 defines the free stoppa
e of the drive mechanism, independent o
the stopping behavior selected, which is stipulated with the parameter Stop function
630.
Attention!
Monitoring of the analog input signal via the parameter
rror/Warnin
Behavior
563 demands a check of the characteristic parameters.